Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/10/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CHECK BEFORE FINAL -- CONTACTORS OK TO TILE. |
|
| 10/06/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH #1 & 7 PREVIOUS ITEM |
|
| 10/04/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SUPPORT WIRES FOR VDV TO BE ATTACHED BOTH ENDS 300.11 2. SUPPORT WIRES NEEDED FOR EXIT SIGNS 3. NO MORE THAN 360 DEG. IN A CONDUIT RUN 4. REMOVE BONDING JUMPER AT SUB-PANEL 5. IF SUPPORTED FIXTURES WHIPS AS PER 300.11 6. INSTALL BONDING JUMPER AT DISCONNECT 7. NEED R PINS 8. INSTALL CONDUCTORS LINE SIDE |