Permit: T06CM04342

Parcel: 12905401D


Addresses:

2055 E 19TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/23/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE ROOF ACCESS
2. INSTALL NEW GROUNDING PER PLAN FOR SERVICE, BOND NEW WATER LINE, GAS IF APPLICABLE
3. 2 NEW DISCONNECTS AT SERVICE, INSTALL NEUTRAL IN DISCONNECTS & TERMINATE PER NEC
4. SUPPORT 3/4" EMT PER CODE AT AC DISCONNECT AT SERVICE, WITHIN 3' OF TERMINATION