Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE ROOF ACCESS 2. INSTALL NEW GROUNDING PER PLAN FOR SERVICE, BOND NEW WATER LINE, GAS IF APPLICABLE 3. 2 NEW DISCONNECTS AT SERVICE, INSTALL NEUTRAL IN DISCONNECTS & TERMINATE PER NEC 4. SUPPORT 3/4" EMT PER CODE AT AC DISCONNECT AT SERVICE, WITHIN 3' OF TERMINATION |