Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* THE 2X6 BOARD IN THE HALLWAY IS BEING SUPPORTED BY THE CONDUIT - SHOULDN'T IT BE THE OTHER WAY AROUND? |
|
| 02/21/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* SUPPORT METHODS NOT APPROVED CABLES STILL LAYING ON GRID OR LIGHTS, J-BOXES NOT SUPPORTED PROPERLY GRID WIRES RUN HORIZONTAL FROM WALL STUDS TO J-BOX NOT APPROVED METHOD. SUPPORT RIGIDLY FROM STRUCTURE - SEE 300H NEC |
|
| 02/13/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SUPPORT J-BOXES, PLUG UNUSED OPENINGS. 2. SEE NOTE #2 INSP. 2/1/07 - CABLES |
|
| 02/01/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK SHOWROOM - CEILING LIFT CABLES OFF CEILING TWO AREAS |
|
| 01/17/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | 1. PROVIDE APPROVED ELECTRICAL LIGHTING PLAN 2. CLOSE UP OR ABANDON UNUSED CONDUIT, WIRING, CABELING, NEW LTG. NOT ROUGHED IN YET? OK RESTROOM HARD LIDS |