Permit: T06CM04341

Parcel: 130140260


Addresses:

4188 E 22ND ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/01/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
02/27/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST WASTE & VENT THRU ROOF OK
EVERYWHERE EXCEPT CEILING OF RESTROOM
WATER & PIPING INTERIOR OF BUILDING ONLY OK
(1) SHALL SEE RETEST OF ABOVE CEILING VENT IN RESTROOM (LEAKING)
02/13/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
309-6025 LARRY

PROVIDE TESTING ON ALL PIPING
SEE NOTES FROM 2/9/07 INSP
02/09/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE WATER OR AIR TEST ON ALL PIPING.
2. SHALL PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR HORIZONTAL X HORIZONTAL.
3. SHALL PROVIDE CLEANOUT FOR SINKS.
4. PROVIDE BANG PLATES & FHA STRAPS WHERE REQUIRED.
5. SHALL SUPPORT OVERHEAD PIPING CORRECTLY WITH APPROVED HANGERS AT CORRECT INTERVALS.
6. COPPER PIPING TO BE SECURE & HAVE ISOLATION FROM METAL STUDS.
7. LAV REQUIRES 1 1/2 DRAIN ARM NOT TO EXCEED 42"
NOTE: H/C STOOL REQUIRES 16"-18" SIDE WALL CLEARANCE.
8. PROVIDE MID SPAN SUPPORT FOR VERTICAL VENTS WITH APPROVED CLAMPS.
9. INSTALL WATER PIPING PER PLAN.
02/05/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS AT 8:55 AM