Permit: T06CM04341

Parcel: 130140260


Addresses:

4188 E 22ND ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
01/09/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
WATER TEST UNDERGROUND ONLY WITH COPPER LOOPED UNDER SLAB OK
PIPE WRAPS OK
01/08/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE MINIMUM FALL REQUIRED ON PIPING
2% 3" & BELOW
WATER IN DITCH
PROVIDE DRY AREA IN & AROUND PIPING & FITTINGS.
01/04/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
LOCKED 9 AM
01/03/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. TEST TO BE ON PRIOR TO INSPECTION
2. VENT TAKE-OFFS SHALL BE INSTALLED AT 45 DEG. FROM HORIZONTAL.
3. HORIZONTAL VENTING IS ONLY ALLOWED IF SHOWN ON PLAN OR IF STRUCTURAL CONDITIONS EXIST.
4. CHECK YOUR SLOPE.
12/19/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL INSTALL DRAINAGE PIPING PER PLAN WITH CORRECT VENTING & VENT FITTINGS FOR HORIZONTAL VENTING BELOW FLOOD RIM OF FIXTURE.
2. T/K COPPER IS SPEC. FOR UNDERSLAB WATER PIPING, PROVIDE STAMPED LETTER FROM ENGINEER GIVING OK FOR PEX UNDERGROUND.