Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04341

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/19/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
NEC 110.3
2. NEED UPDATED PANEL SCHEDULE NEC 408.4
3. INSTALL TIE WIRES ON 2X4 LIGHT FIXTURE AT OPPOSITE CORNERS
4. VERIFY LISTING OF WATER VENDING MACHINE. DO NOT SEE LISTING LABEL.