Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL NEC 110.3 2. NEED UPDATED PANEL SCHEDULE NEC 408.4 3. INSTALL TIE WIRES ON 2X4 LIGHT FIXTURE AT OPPOSITE CORNERS 4. VERIFY LISTING OF WATER VENDING MACHINE. DO NOT SEE LISTING LABEL. |