Inspection History Details
Permit: T06CM04333
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK ROUGH |
|
| 11/28/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NO NEW DUCT WORK 1. SECURE NM CABLE IN ATTIC AS PER CODE 2. SUPPORT NM AS IT EXITS WALL TO CONDUIT 3. BRING GROUND WIRE INTO BACK OF BOX OK WALLS |
|
| 11/20/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. WALLS THAT WERE OPEN NEED TO BE REOPENED FOR INSPECTION AS DISCUSSED. 2. INSTALL SMOKE DETECTORS 3. WILL NEED APPROVED EXTENDER RINGS FOR BOXES MORE THAN 1/4" FROM BOX TO SURFACE -- 314.2 4. FILL UNUSED OPENINGS IN BOXES. |