Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM04330

Parcel: 137055070

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04330

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/30/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/29/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. NEED TO VERIFY EM. OR EGRESS LITG. PER PLAN AND OPERABLE
2. PROVIDE APPROVED PLANS
3. CALLED SUMMIT (KEVIN) LEFT MESSAGE
04/22/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOND WATER & STEEL
2. IDENTIFY SERVICE DISCONNECT
3. INSTALL ALL CABLES
4. PROVIDE TORQUE LETTER
5. PATCH CONCRETE