Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
04/12/2007 BUILDING - FINAL Approved IVRS - Inspection :*
01/31/2007 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) OUTDOOR LIGHTING FIXTURES DO NOT MEET OUTDOOR CODE-SEE 1/29/07 INSPECTION. CORRECTIONS MUST BE MADE BY 2/15/07
2) OK TO OCCUPY HOME
01/30/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRIC 50 AMP CIRCUIT IS NOT PER CODE SEE 1/29/07 INSPECTION
2) OUTSIDE ELECTRIC LIGHTS DO NOT MEET OUTSIDE LIGHTING CODE. SEE 1/29/07 INSPECTION
01/29/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRIC SUB PANEL ON PORCH REQUIRES AN ISOLATED NEUTRAL BAR
2) ELECTRIC SUB PANEL IS MISSING A DEAD FRONT
3) SPA DISCONNECT MUST HAVE A GFCI CIRCUIT BREAKER
4) SPA CIRCUIT MUST HAVE AN INSULATED GROUND
5) ROOF MOUNTED HEAT PUMP MUST HAVE LABELS MARKED FOR APPLICABLE HEAT STRIP KIT/FUSE
6) OUTSIDE LIGHTING DOES NOT MEET OUTSIDE LIGHTING CODE. LOT IS .0916 ACRES. YOU ARE ALLOWED 5038 TOTAL LUMENS INCLUDING 1099 UNSHIELDED LUMENS. YOU HAVE 4-100 WATT (1700 LUMEN) FIXTURES FOR A TOTAL OF 6900 LUMENS. IF YOU FEEL YOUR FIXTURES ARE FULL CUT OFF FIXTURES THEN PROVIDE PROOF PER PARAGRAPH 4.7 OF THE OUTDOOR LIGHTING CODE