Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 01/31/2007 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) OUTDOOR LIGHTING FIXTURES DO NOT MEET OUTDOOR CODE-SEE 1/29/07 INSPECTION. CORRECTIONS MUST BE MADE BY 2/15/07 2) OK TO OCCUPY HOME |
|
| 01/30/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRIC 50 AMP CIRCUIT IS NOT PER CODE SEE 1/29/07 INSPECTION 2) OUTSIDE ELECTRIC LIGHTS DO NOT MEET OUTSIDE LIGHTING CODE. SEE 1/29/07 INSPECTION |
|
| 01/29/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRIC SUB PANEL ON PORCH REQUIRES AN ISOLATED NEUTRAL BAR 2) ELECTRIC SUB PANEL IS MISSING A DEAD FRONT 3) SPA DISCONNECT MUST HAVE A GFCI CIRCUIT BREAKER 4) SPA CIRCUIT MUST HAVE AN INSULATED GROUND 5) ROOF MOUNTED HEAT PUMP MUST HAVE LABELS MARKED FOR APPLICABLE HEAT STRIP KIT/FUSE 6) OUTSIDE LIGHTING DOES NOT MEET OUTSIDE LIGHTING CODE. LOT IS .0916 ACRES. YOU ARE ALLOWED 5038 TOTAL LUMENS INCLUDING 1099 UNSHIELDED LUMENS. YOU HAVE 4-100 WATT (1700 LUMEN) FIXTURES FOR A TOTAL OF 6900 LUMENS. IF YOU FEEL YOUR FIXTURES ARE FULL CUT OFF FIXTURES THEN PROVIDE PROOF PER PARAGRAPH 4.7 OF THE OUTDOOR LIGHTING CODE |