Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/06/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SELF-TAPPING SCREWS ARE NOT AN ALLOWED METHOD OR ATTACHING EQUIP. GROUNDING LUGS. 2. E.M.T CONDUIT NEEDS PROPER E.M.T CONNECTORS. 3. CONDUIT NEEDS TO BE SECURED WITHIN 3' OF ANY BOX, LB, COUPLING, PANEL, ETC. 4. GLAND MISSING FROM 1" E.M.T CONNECTOR. |