Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM04300
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/22/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/01/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE APPROVED PLAN WITH WIRING METHOD FOR SUMP PUMP - USE SCH 80 PVC WHERE EXPOSED, AND NOT SUBJECT TO PHYSICAL DAMAGE IN LIEU OF SCH.40 PER COT ORDIN. - PLASTIC RECEPT. COVER NOT APPROVED IN TRAFFIC AREA |
|
03/31/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK FEEDERS &* TERMINATION INTO SES, CHECK REQUIREMENTS FOR WITH OR WITHOUT MCB'S FOR PANELS IN SPACES - HAVE TEMP CONST. POWER ADDED TO PERMITS OR TEMP POWER FOR TESTING BOND POSTED - LABEL MAIN FUSES DISCONNECTS & PANELS IN SPACES |
|
03/13/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* STILL NEED LETTER OF TORQUE OK TO CLEAR TEC COMMERCIAL OWNERS METER |
|
02/27/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BRACE SECONDARY'S IN SERVICE CABINET AS INDICATED BY MANUF. SEE INSTRUCTIONS INSIDE PANEL 2. PROVIDE LETTER OF TORQUE 3. POST BOND FOR TEMP POWER FOR TEST 4. OK GROUNDING |
|
02/20/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONTR. NOT ON SITE CALLED PER REQUEST NO ANSWER RECALL INSP. |