Permit: T06CM04283

Parcel: 13216060A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM04283

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/11/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
10/03/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
09/26/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
UNIT #3
1. GAS PIPING TO BE MINIMUM 3" ABOVE FINISH GRADE AND SHALL BE RIDGID PIPING INTO WEATHERPROOF ENCLOSURE.
2. PROVIDE COUNTER FLASHING FOR VENT THRU ROOF JACK.
3. PROVIDE APPROVED VENT CAP FOR DOUBLE WALL VENT PIPING.

UNIT #5
1. PROVIDE APPROVED BASE FOR WATER HEATER
2. GAS PIPING SHALL BE MINIMUM 3" ABOVE FINISH GRADE AND BE RIDGID INTO WEATHERPROOF ENCLOSURE.
3. PROVIDE COUNTER FLASHING FOR VENT THRU ROOF NOT TAPE.
4. PROVIDE APPROVED DOUBLE WALL VENT CAP.
REMOVE FLAMMABLE SUBSTANCE FROM ALL VENT PIPING BOTH UNITS.
08/08/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*