Permit: T06CM04272

Parcel: 12709011E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/25/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/23/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH ROOF & 1ST FLOOR MECH ROOM
2. SUPPORT CONDUIT 6TH FLOOR MECH ROOM
3. CORRECTLY LABEL PANEL
01/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LABEL DISCONNECT
2. STRAP FLEX CONDUIT BELOW FLOOR
3. PLEASE VERIFY LISTING FOR FLEX CONDUIT WITH 480V

ROOF:
1. WHICH FLOOR IS UNIT SERVING
2. MAINTAIN WORKING SPACE 110.26
3. GROUND LUG TO MAKE SURFACE CONTACT ALSO CLEAN SURFACE.
4. NO MORE THAN 360 DEG. IN A CONDUIT RUN.

MECH ROOM:
1. CLEAN SURFACE UNDER GROUND BAR.