Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04272
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/23/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH ROOF & 1ST FLOOR MECH ROOM 2. SUPPORT CONDUIT 6TH FLOOR MECH ROOM 3. CORRECTLY LABEL PANEL |
|
01/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LABEL DISCONNECT 2. STRAP FLEX CONDUIT BELOW FLOOR 3. PLEASE VERIFY LISTING FOR FLEX CONDUIT WITH 480V ROOF: 1. WHICH FLOOR IS UNIT SERVING 2. MAINTAIN WORKING SPACE 110.26 3. GROUND LUG TO MAKE SURFACE CONTACT ALSO CLEAN SURFACE. 4. NO MORE THAN 360 DEG. IN A CONDUIT RUN. MECH ROOM: 1. CLEAN SURFACE UNDER GROUND BAR. |