Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM04257

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/29/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
09/20/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MC CABLE TO BE SUPPORTED PER CODE
2. J-BOXES TO BE SUPPORTED TO STRUCTURE. DO NOT SUPPORT TO OTHER TRADE SUPPORTS.
3. ALL LV CABLING TO BE SUPPORTED AND OFF GRID PER
NEC 725-800, ANY ABANDONED CABLE TO BE REMOVED IN CEILING WHERE EXPOSED.
4. SOME 2X4 FIXTURES DO NOT HAVE SEISMIC WIRES.
5. PROVIDE 8' LADDER FOR INSPECTION.
6. THERE ARE MANY J-BOXES, CONDUITS, NOT SUPPORTED PER CODE THAT MAY HAVE BEEN EXISTING - INFORM OWNER.
09/18/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*