Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/15/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NOTE: PROVIDE LETTER FROM ENGINEER CONCERNING DELETION OF EXTERIOR EMERGENCY LIGHTING. |
|
| 12/13/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND ALL EQUIPMENT AND BOXES WITH EQUIPMENT GROUND. 2. FILL UNUSED OPENINGS 3. USE PROPER EMT CONNECTOR INTO BOXES 4. TIGHTEN ALL LOOSE DEVICES 5. HAVE OVERFILLED J-BOXES 6. EMERGENCY LIGHTING NOT WORKING AND NEEDS TO BE ON LIGHTING CKT FOR THAT AREA. 7. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED AND NUMBER BREAKERS. 8. SEAL UNUSED RACEWAYS OUT OF PANEL 9. AT ROOFTOP UNIT - IDENTIFY SERVICE LABEL, GROUND DISCONNECT AND DISCONNECT NOT ALLOWED TO BLOCK ACCESS PANEL - CHECK WITH MECHANICAL INSPECTOR. |
|
| 11/29/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |