Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM04249
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/03/2007 | FRAMING | Approved | IVRS - Inspection :* | |
01/02/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OK TO INSULATE 2) DUCT RESTRICTED IN POWER ROOM |
|
12/29/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 2, 7 & 12 FROM 12/22/06 NOT DONE 2) NO PLAN PERMIT ON SITE |
|
12/22/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STUCCO NOT COMPLETE 2. PROVIDE CITY OF TUCSON DETAIL FOR 4X4 POST ON INTERIOR BEARING POINT OF TRIPPLE GIRDER POST FROM ROOF NOT ON PLAN 3. SEARING STUD OVERNOTCHED AT WATER SERVICE 4. NAIL PROTECT PLUMBING WITH 1 1/4" OF WALL SURFACE 5. WIRES MUST TERMINATE IN APPROVED BOXES 6. FIRE STOP FLOOR PENETRATIONS 7. DUCT RESTRICTING ABOVE POWDER ROOM 8. ANCHOR KITCHEN WALL AT TOP 9. FIRE STOP REQUIRED AT 10FT INTERVALS 10. SHIM HEADERS 11. FIRE STOP CHASE - LAUNDRY 12. NAIL SHEAR WALL BOTTOM PLATES 13. BATH FAN NOT WIRED 14. MAKE UP AIR INTAKE MUST BE 10 FT FROM SEWER VENT |