Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BREAKER TO BE LISTED FOR USE BY MANUFACTURER 2. DO NOT FORK CONDUCTOR -- INSTALL ALL STRANDS UNDER TERMINATION. 3. BREAKER AMPACITY TO BE SIZED PER CONDUCTOR SIZE 4. PLEASE VERIFY GROUND RODS (2) 5. LABEL ALL BREAKERS |