Permit: T06CM04238


Addresses:

2502 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM04238

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/07/2007 ELECTRIC - INTERMEDIATE Approved
06/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK PREVIOUS CORRECTIONS
04/04/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
1. PROVIDE TORQUE LETTER -- NEC 110.3B
2. SECURE EQUIPMENT TO SLAB -- NEC 110.13A
3. NEED BUSHINGS ON PNL - NEC 352.46
4. IDENTIFY SERVICE DISCONNECT - NEC 230.70B
5. IDENTIFY ALL METERS, ADDRESSES - CITY
6. BOND GAS PIPE, WATER PIPE, EXPOSED METAL DRAIN PIPE
NEC 250.102
7. PROVIDE PROTECTION FOR SERVICE FROM TRAFFIC - NEC 110.26F2
01/29/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*