Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM04238
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2007 | ELECTRIC - INTERMEDIATE | Approved | ||
| 06/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PREVIOUS CORRECTIONS |
|
| 04/04/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. PROVIDE TORQUE LETTER -- NEC 110.3B 2. SECURE EQUIPMENT TO SLAB -- NEC 110.13A 3. NEED BUSHINGS ON PNL - NEC 352.46 4. IDENTIFY SERVICE DISCONNECT - NEC 230.70B 5. IDENTIFY ALL METERS, ADDRESSES - CITY 6. BOND GAS PIPE, WATER PIPE, EXPOSED METAL DRAIN PIPE NEC 250.102 7. PROVIDE PROTECTION FOR SERVICE FROM TRAFFIC - NEC 110.26F2 |
|
| 01/29/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |