Permit: T06CM04238


Addresses:

2502 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06CM04238

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2007 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
1. GROUND RODS & GAS & WATER 3/0 COPPER
2. 5 - 2 1/2" PVC FEEDERS FROM NEW SW GEAR
3. 2 - 2" PVC CABLE CONDUITS
4. 1 - 4" PVC COMM CONDUIT
5. 7 - 1" PVC PHONE CONDUITS

OK NORTH HALF OF UNDERGROUND
02/22/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. GROUND RODS TO BE DRIVEN TO A DEPTH OF 8', THEN CONNECT GROUNDING ELECTRODE CONDUCTOR AND STUB CONDUCTOR INTO GEAR.
2. REVISE PERMIT TO ACTUAL ADDRESSES

OK TO COVER ALL AREAS
EXCEPT RODS/BONDING
01/29/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*