Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06CM04238
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* 1. GROUND RODS & GAS & WATER 3/0 COPPER 2. 5 - 2 1/2" PVC FEEDERS FROM NEW SW GEAR 3. 2 - 2" PVC CABLE CONDUITS 4. 1 - 4" PVC COMM CONDUIT 5. 7 - 1" PVC PHONE CONDUITS OK NORTH HALF OF UNDERGROUND |
|
| 02/22/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. GROUND RODS TO BE DRIVEN TO A DEPTH OF 8', THEN CONNECT GROUNDING ELECTRODE CONDUCTOR AND STUB CONDUCTOR INTO GEAR. 2. REVISE PERMIT TO ACTUAL ADDRESSES OK TO COVER ALL AREAS EXCEPT RODS/BONDING |
|
| 01/29/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* |