Permit: T06CM04227

Parcel: 140152020


Addresses:

2118 E CANADA ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/24/2014 FRAMING Approved IVRS - Inspection :*
03/24/2014 FRAMING Approved CORRECTIONS DATED 08/20/07 ADDRESSED THROUGH OTHER INSPECTIONS (SEE APPROVALS)
02/03/2009 FRAMING Partial Approval IVRS - Inspection :*
OK TO INSULATE & SHEETROCK
08/20/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LIGHT BOX IN BEDROOM OVER LOADED WITH WIRES
2) PROTECT ALL WIRES ENTERING TO J-BOXES
3) GROUND ALL METAL BOXES
4) ROUTE ALL WIRES CONNECTED TO UNDER SIDE OF RAFTERS
5) PVC LINE WATER NOT ALLOWED IN BETWEEN FRAMING
6) EXPOSE ALL FRAME AND ELECTRIC COVERED WITH SHEETROCK
7) NAIL EXTERIOR SHEATHING AS REQUIRED PER MANUFACTURERS SPECS