Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04202
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/23/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. TIGHTEN RACEWAY SET SCREWS 2. INSTALL L.B COVER 3. EMT TO BE STRAPPED WITHIN 3' OF BOXES 4. REMOVE UNUSED BOND STRAP IN METER BASE 5. REMOVE UNUSED GROUNDING ELECTRODE CONDUCTOR 6. SEAL UNUSED OPENING INSIDE OF METER BASE 7. SEAL OPENING IN DISCONNECT 8. WHERE IS GROUNDING ELECTRODE FOR SERVICE? IS ONE REQUIRED. CALL ME @ 349-5029 |
|
08/16/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED TO COMPLETE SCOPE OF WORK AS OUTLINED ON PLAN INCLUDING ALL DEMOLITION/REMOVAL OF EXISTING EQUIPMENT. |
|
08/15/2006 | ELECTRIC - FINAL | Cancelled | CANCELLED PER DENNIS OF CALDWELL CONST. #909-5681 | |
08/15/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/11/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* MAKE SURE SCOPE OF WORK IS AS PER PLAN AND CALL WHEN ALL IS COMPLETE. |