Permit: T06CM04202

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04202

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/23/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. TIGHTEN RACEWAY SET SCREWS
2. INSTALL L.B COVER
3. EMT TO BE STRAPPED WITHIN 3' OF BOXES
4. REMOVE UNUSED BOND STRAP IN METER BASE
5. REMOVE UNUSED GROUNDING ELECTRODE CONDUCTOR
6. SEAL UNUSED OPENING INSIDE OF METER BASE
7. SEAL OPENING IN DISCONNECT
8. WHERE IS GROUNDING ELECTRODE FOR SERVICE? IS ONE REQUIRED.

CALL ME @ 349-5029
08/16/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NEED TO COMPLETE SCOPE OF WORK AS OUTLINED ON PLAN INCLUDING ALL DEMOLITION/REMOVAL OF EXISTING EQUIPMENT.
08/15/2006 ELECTRIC - FINAL Cancelled CANCELLED PER DENNIS OF CALDWELL CONST. #909-5681
08/15/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/11/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
MAKE SURE SCOPE OF WORK IS AS PER PLAN AND CALL WHEN ALL IS COMPLETE.