Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 08/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED MAKE SURE EACH BREAKER IS NUMBERED AND GOINT WHAT IT SAYS IT'S GOING TO. |
|
| 08/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE HAVE SOMEONE PRESENT TO ACCESS ABOVE CEILING FOR INSPECTION. 2. AREA OCCUPIED WITHOUT APPROVAL OR CLEARANCE. |
|
| 08/11/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH ITEMS 4, 5, 8, 9, 10 ALSO LETTER FROM ARCHITECT |
|
| 08/10/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CLEAN FOREIGN MATERIAL FROM PANEL 110.12 2. FILL UNUSED OPENINGS IN PANEL & JUNCTION BOXES 110.12 3. SEPARATE GROUNDS AND NEUTRALS AT PANELS 4. REVISE PANEL DIRECTORY 5. USE BREAKER LISTED FOR USE BY MANUFACTURER 6. MISSING JUNCTION BOX COVERS 7. VERIFY BOX FILL 8. VDV CABELING TO BE AS PER 725.3, 725.6, 760.6, 800.6, 800.3 9. FIXTURES TO BE ATTACHED TO GRID 410.16 10. SUPPORT WIRES NEEDED FOR FIXTURES |