Permit: T06CM04201

Parcel: 125110570


Addresses:

3833 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/17/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
08/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED MAKE SURE EACH BREAKER IS NUMBERED AND GOINT WHAT IT SAYS IT'S GOING TO.
08/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLEASE HAVE SOMEONE PRESENT TO ACCESS ABOVE CEILING FOR INSPECTION.
2. AREA OCCUPIED WITHOUT APPROVAL OR CLEARANCE.
08/11/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH ITEMS 4, 5, 8, 9, 10 ALSO LETTER FROM ARCHITECT
08/10/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CLEAN FOREIGN MATERIAL FROM PANEL 110.12
2. FILL UNUSED OPENINGS IN PANEL & JUNCTION BOXES 110.12
3. SEPARATE GROUNDS AND NEUTRALS AT PANELS
4. REVISE PANEL DIRECTORY
5. USE BREAKER LISTED FOR USE BY MANUFACTURER
6. MISSING JUNCTION BOX COVERS
7. VERIFY BOX FILL
8. VDV CABELING TO BE AS PER 725.3, 725.6, 760.6, 800.6, 800.3
9. FIXTURES TO BE ATTACHED TO GRID 410.16
10. SUPPORT WIRES NEEDED FOR FIXTURES