Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM04197
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
04/10/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE SECONDARY DRAIN ON AIR HANDLER 2. DUCT SMOKE DETECTORS NOT COMPLETE 3. PROVIDE DAMPER ON OUTSIDE DUCTS 4. PROVIDE APPROVED SEALERS ON DUCT 5. ALL PVC JOINTS TO BE PRIMED AND GLUED 6. REMOVE ALL FOIL TAPE FROM FLUE VENTS 7. SEAL ALL JOINTS ON MECHANICAL ROOM DUCTS 8. REFRIGERATION PIPING NOT PROPERLY INSULATED 9. LOW VOLTAGE CONTROL WIRING MUST BE PROTECTED 10. REGISTER FALLING FROM CEILING AT ENTRY WAY |