Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM04197

Parcel: 129010360


Addresses:

300 S TUCSON BL 09


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM04197

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/22/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/10/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE SECONDARY DRAIN ON AIR HANDLER
2. DUCT SMOKE DETECTORS NOT COMPLETE
3. PROVIDE DAMPER ON OUTSIDE DUCTS
4. PROVIDE APPROVED SEALERS ON DUCT
5. ALL PVC JOINTS TO BE PRIMED AND GLUED
6. REMOVE ALL FOIL TAPE FROM FLUE VENTS
7. SEAL ALL JOINTS ON MECHANICAL ROOM DUCTS
8. REFRIGERATION PIPING NOT PROPERLY INSULATED
9. LOW VOLTAGE CONTROL WIRING MUST BE PROTECTED
10. REGISTER FALLING FROM CEILING AT ENTRY WAY