Permit: T06CM04197

Parcel: 129010360


Addresses:

300 S TUCSON BL 09


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM04197

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
05/22/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE BACK FLOW CERT FOR IRRIGATION
04/17/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE CLEANOUT AT TIE IN FROM RESTROOMS
2. PROVIDE BACKFLOW AT BUILDING FOR IRRIGATION
3. COMPLETE LIST #1, #7, #10 BEFORE CALLING FOR FINAL
4. COMPLETE TIE IN AT HUMIDIFIER IN BACK ROOM
04/10/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. DRINKING FOUNTAIN NOT WORKING
2. DOOR LOCKED UNABLE TO INSPECT HUMIDIFIER
3. COMPLETE LIST NUMBERS 1, 2, 4, 7, 10
4. HAVE PLUMBER OR CONTRACTOR ON SITE FOR INSPECTION
04/02/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. MAKE ALL CLEANOUTS WATER & GAS TIGHT
2. ALL FIXTURES TO BE WORKING
3. PROVIDE FLUE VENT FOR WATER HEATER
4. SECURE FAUCET FOR MOP SINK AND COMPLETE DAPPING OF MOP SINK
5. YARD WATER TO HUMIDIFIER PVC CANNOT BE ABOVE GROUND
6. PROVIDE VACUUM BREAKERS AT ALL HOSE BIBS
7. ADD SUPPORT ON GAS PIPING IN NORTH MECH ROOM
8. ADD SUPPORT FOR MIXING VALVE UNDER LAVS
9. LIST MAY NOT BE COMPLETE
10. PROVIDE CLEAN BACTERIAOLOGICAL REPORT
11. GAS PSI TEST NOT HOLDING