Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM04197
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
05/22/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE BACK FLOW CERT FOR IRRIGATION |
|
04/17/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE CLEANOUT AT TIE IN FROM RESTROOMS 2. PROVIDE BACKFLOW AT BUILDING FOR IRRIGATION 3. COMPLETE LIST #1, #7, #10 BEFORE CALLING FOR FINAL 4. COMPLETE TIE IN AT HUMIDIFIER IN BACK ROOM |
|
04/10/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. DRINKING FOUNTAIN NOT WORKING 2. DOOR LOCKED UNABLE TO INSPECT HUMIDIFIER 3. COMPLETE LIST NUMBERS 1, 2, 4, 7, 10 4. HAVE PLUMBER OR CONTRACTOR ON SITE FOR INSPECTION |
|
04/02/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MAKE ALL CLEANOUTS WATER & GAS TIGHT 2. ALL FIXTURES TO BE WORKING 3. PROVIDE FLUE VENT FOR WATER HEATER 4. SECURE FAUCET FOR MOP SINK AND COMPLETE DAPPING OF MOP SINK 5. YARD WATER TO HUMIDIFIER PVC CANNOT BE ABOVE GROUND 6. PROVIDE VACUUM BREAKERS AT ALL HOSE BIBS 7. ADD SUPPORT ON GAS PIPING IN NORTH MECH ROOM 8. ADD SUPPORT FOR MIXING VALVE UNDER LAVS 9. LIST MAY NOT BE COMPLETE 10. PROVIDE CLEAN BACTERIAOLOGICAL REPORT 11. GAS PSI TEST NOT HOLDING |