Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04197
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/04/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
04/18/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
04/17/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
12/03/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |