Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM04197
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2008 | BUILDING - FINAL | Approved | ||
08/06/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED ELECTRIC FINAL |
|
04/17/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEEDS FIRE, MECH, PLUMBING, ELEC FINALS 1. BATHROOM ADA SIGNAGE 60" TO CENTER OF SIGN 2. LOUVRED EXIT DOOR (32" MIN. ) 404.2.2 NOT ON PLAN 3. INSTALL TRUNCATED DOMES PER PLAN AND OUTSIDE MAIN ENTRANCE WITH ASPHALT ROMPED TO SIDE WALLS 4. NEED PAGE WITH OCC. LOAD, REQ EXITS |