Permit: T06CM04197

Parcel: 129010360


Addresses:

300 S TUCSON BL 09


Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T06CM04197

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
05/02/2007 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
THIS INSPECTION COVERS PERIMETER FOUNDATION IN ACCORDANCE WITH APPROVED PLANS AND SPEC. DETAIL
S1 & S2 SHEETS SPECIAL INSPECTION FOR EPOXY CONNECTIONS PROVIDED
04/26/2007 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEW VAULT, PROVIDE SPECIAL INSPECTION REPORT FOR EPOXY CONNECTION ON EXISTING FOUNDATION
PROVIDE VERTICAL REBAR ON CORNERS AT LEAST 3 ON EACH CORNER
PROVIDE MASONRY CONTROL JOINT REBAR ON WEST AND EAST SIDES AT LEAST 2 #5 ON EACH SIDE OF MASONRY CONTROL JOINT.