Permit: T06CM04164

Parcel: 125011200


Addresses:

3033 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04164

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
(1) PANEL DIRECTORY IS NOT CORRECTLY IDENTIFIED -
NEC 408.4

WILL NEED TO PAY REINSPECTION FEE PRIOR TO FINAL APPROVAL.

DIRECTORY MUST GO TO CKTS IT SAYS ITS GOING TO
11/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL DIRECTORY NEEDS TO BE IDENTIFIED PROPERLY AND CLEARLY -- SEE PANEL SCHEDULE ON PLANS.
2. TIGHTEN LOOSE 2ND FLOOR RECEPTACLE.
11/14/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WILL RESCHEDULE
11/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE CONTRACTOR ON SITE -- WILL RESCHEDULE
10/12/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH OFFICE FURNITURE CONNECTIONS
2. FINISH PROPERLY LABELING BREAKERS #2 PREVIOUS INSPECTION.
10/11/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HAVE OPEN NEUTRALS ON CKT'S
2. PROPERLY IDENTIFY ALL NEW CKT'S IN PANEL
3. CKT'S TO FEED RECEPTACLES PER PLAN.
4. PLAN CALLS FOR ISOLATED GROUNDS, YOU HAVE EQUIPMENT GROUNDS ONLY -- MODULAR FURNITURE NOT INSTALLED @ THIS TIME.