Permit: T06CM04148


Addresses:

308 W GLENN ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/04/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/01/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
DUCT SMOKE DETECTOR TEST ON 4 SYSTEMS OK
AIR BALANCE REPORT DOES NOT REFLECT OUTSIDE AIR QUANTITIES
07/25/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE AIR BALANCE REPORT
2. PROVIDE DUCT SMOKE DETECTOR TEST
3. AC 5 HAS NOT ECONOMISER/OUTSIDE AIR
4. FLASHING AT AC-5 NOT COMPLETE