Permit: T06CM04148


Addresses:

308 W GLENN ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04148

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/18/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. DISCONNECTING MEANS FOR WATER
2. BOX OVER 1/8" 314.21
3. FUSES AT DH-1

OK FINAL AFTER CORRECTIONS
11/12/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK LOCKER ROOMS

1. BOXES MORE THAN 1/4" -- 314.20
2. ARE EM & EXIT AT STORAGE PER 700.12(F)
08/08/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF:
1. SECURELY MOUNT MAINTENANCE RECEPTACLE
2. GROUND LUG TO MAKE SURFACE CONTACT
3. GFCI TO WORK WITH DISCONNECT OFF

BLDG:
1. FINISH WEST SIDE OUTSIDE
2. FINISH PREVIOUS INSPECTION ITEMS

PARKING LOT:
1. BOND POLES PER 250.54
08/07/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
08/06/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CLEARANCES PAINT AND FOREIGN MATERIAL FROM DEVICE TERMINALS
2) DRINKING FOUNTAIN OUTLET NOT ACCESSIBLE
3) FINISH EXTENDER RINGS 314.20 & 21
07/30/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WAREHOUSE:
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE
2. FILL UNUSED OPENINGS
3. FIRE ALARM BOXES TO BE IDENTIFIED RED 760