Permit: T06CM04148


Addresses:

308 W GLENN ST


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM04148

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/18/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/17/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 1ST FLOOR

1. CENTER IS CENTER
07/14/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. FIRE ALARM FLEX SUPPORT 4' & 12"
2. LABEL DISCONNECT

OK 2ND FLOOR AFTER CORRECTIONS
07/10/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SECURELY ATTACH FIXTURES TO GRID 410.16
2. MAINTAIN WORKING CLEARANCES A/C DISCONNECT
3. SUPPORT VDV CABLING 725.24, 800.24, 300.11
4. SUPPORT M/C CABLE WITHIN 12" OF BOXES
5. SEAL UNUSED CONDUIT OPENING
6. CLOSE BOXES
7. REMOVE TEMP LIGHTING
04/11/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*