Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T06CM04148
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2007 | ELECTRIC - UFER | Approved | IVRS - Inspection :* 1. 2 GROUND RODS 6' APART -- 4/0 COPPER ALSO, 4/0 TAIL CALDWELDED TO EXIST BLDG. GROUND |