Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/23/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE COVERS OVER CANVAS CONNECTORS 2. VENTS TO BE DOWNSTREAM OF CONDENSATE TRAPS 3 OF THE TRAPS ARE BACKWARDS. 3. SEAL JOINTS ON EXPOSED DUCT 4. PERMANENTLY I.D EQUIPMENT ON ROOF. |
|
| 01/17/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* OK TO FILE FOR TEMP C OF O |