Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04127
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
01/19/2007 | ELECTRIC - ABOVE CEILING | Cancelled | CANCELLED PER BUCK OF KOLBY GALLAGHER CONST. #465-1366 | |
01/19/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
01/17/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
01/12/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. DERATE CONDUCTORS IN RACEWAYS AS REQUIRED BY NEC 310.15 2. SECURE ALL FIXTURE TO GRID AND INSTALL SUPPORT WIRES NEC 300.11 3. USE EQUIPMENT GROUND TO GROUND METAL ENCLOSURE NEC 250.122, 314.4 4. HAVE OVERFILLED J-BOXES - NEC 314.16 5. INSTALL K.O BLANKS IN UNUSED OPENING - NEC 314.17 6. INSTALL ALL J-BOX COVERS, FINISH ALL CEILING WING 7. LOW VOLTAGE WIRING TO BE NEAT AND WORKMAN LIKE USING APPROVED HANGERS & FITTINGS SECURED/SUPPORTED BY STRUCTURE NOT EQUIPMENT. 8. PROVIDE ACCEPTABLE PATH FOR EQUIPMENT GROUNDS IN SUB-PANELS |
|
12/13/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |