Permit: T06CM04127

Parcel: 113052570


Addresses:

3499 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM04127

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/19/2007 ELECTRIC - ABOVE CEILING Cancelled CANCELLED PER BUCK OF KOLBY GALLAGHER CONST. #465-1366
01/19/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
01/17/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
01/12/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. DERATE CONDUCTORS IN RACEWAYS AS REQUIRED BY
NEC 310.15
2. SECURE ALL FIXTURE TO GRID AND INSTALL SUPPORT WIRES NEC 300.11
3. USE EQUIPMENT GROUND TO GROUND METAL ENCLOSURE
NEC 250.122, 314.4
4. HAVE OVERFILLED J-BOXES - NEC 314.16
5. INSTALL K.O BLANKS IN UNUSED OPENING - NEC 314.17
6. INSTALL ALL J-BOX COVERS, FINISH ALL CEILING WING
7. LOW VOLTAGE WIRING TO BE NEAT AND WORKMAN LIKE USING APPROVED HANGERS & FITTINGS SECURED/SUPPORTED BY STRUCTURE NOT EQUIPMENT.
8. PROVIDE ACCEPTABLE PATH FOR EQUIPMENT GROUNDS IN SUB-PANELS
12/13/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*