Permit: T06CM04125

Parcel: 10612017R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/31/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/30/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROVIDE INSTALLATION SHEET FOR ALL DIMMERS.
2. HALO CANS SHOULD HAVE LISTED TRIMS FOR CANS SO I CAN VERIFY PROPER BULB/TRIM COMBINATION.
3. DIMMERS NOT ALLOWED ON RECEPTACLES.
4. PANEL DIRECTORYS NEED TO BE CORRECTLY IDENTIFIED - NEC 408.4
5. INSTA-HOT NOT WIRED
6. PROVIDE ROOF ACCESS