Inspection History Details
Inspection Status: Approved
Inspection History: ROOF NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2007 | ROOF NAILING | Approved | IVRS - Inspection :* OK TO DRY IN |
|
| 11/21/2007 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TRUSS CALCS TO VERIFY (2) ON ROOF FRAMING NOTES 2. MISSING "SIMPSON" LTT19 TENSION TIE PER 1/SD1 & 3/SD1 3. SKYLIGHT OPENINGS CALL FOR DOUBLE TRUSS - BLK OUT PER 6/SD1 NOT READY NEED TO FOLLOW PLANS STOPPED INSPECTION |