Inspection History Details
Inspection Status: Not Applicable
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM04104
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Not Applicable
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2008 | ELECTRIC - INTERMEDIATE | Not Applicable | IVRS - Inspection :* | |
04/29/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/14/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION #18 - MISSING LIGHT GLOBE #17 - LIGHT TO HAVE PROPER J-BOX, WALL LAMP HAS SPLICE IN CORD, LIGHT MISSING GLOBE #15 - REPLACE SMOKE DETECTOR EXTERIOR: - PANEL B - CORRECTLY IDENTIFY PANEL DIRECTORY - GFI PROTECT EXTERIOR RECEPTACLES - PANEL A - NOT GROUNDED, PANEL DIRECTORY NOT CORRECT - CHECK FOR PROPERLY SIZED EQUIPMENT GROUNDS - NEC 250.122 - NO GROUND TO PANEL "B"? - NEUTRALS TO SHARE NO MORE THAN 2 CKTS - MULTIWIRE BRANCH CKT'S TO TERMINATE ON SEPARATE PHASES ELECTRICAL CONTRACTOR TO GO THROUGH PLANS AND MAKE SURE ALL CORRECT BEFORE CALLING IN FOR FINAL 440-0536 |