Inspection History Details
Inspection Status: Not Applicable
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2007 | ELECTRIC - SERVICE RELOCATION | Not Applicable | IVRS - Inspection :* | |
| 01/31/2007 | ELECTRIC - SERVICE RELOCATION | Approved | ||
| 11/06/2006 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : The service is not per code.| 210* 1. INSTALL ADDRESS ON SERVICE. 2. PROVIDE FLASHING FOR MAST @ ROOF PENETRATION 3. TIGHTEN ALL RACEWAY FITTINGS. 4. BOND GAS PIPING FOR UNIT (NOT GAS MAIN) 5. BOND UNIT'S WATER PIPE 6. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE OR BURY MINIMUM 12" 7. NEED MINIMUM 3 0 COPPER FOR SERVICE CONDUCTORS (HOT'S) 8. IDENTIFY ALL NEUTRALS AT TERMINATIONS AND CLOSE TO WEATHERHEAD. 9. IDENTIFY SERVICE DISCONNECT. 10. WALL AT SUB-PANEL COVERED WITHOUT INSPECTION. 11. TIGHTEN ALL BUSHINGS AND SET SCREWS. |