Permit: T06CM04085

Parcel: 10612199B


Addresses:

1541 W PRINCE RD


Inspection Status: Not Applicable

Inspection History: ELECTRIC - SERVICE RELOCATION

Permit Number - T06CM04085

Inspection Description - ELECTRIC - SERVICE RELOCATION

Inspection Status - Not Applicable

Date Description Inspector Results Comments
01/31/2007 ELECTRIC - SERVICE RELOCATION Not Applicable IVRS - Inspection :*
01/31/2007 ELECTRIC - SERVICE RELOCATION Approved
11/06/2006 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
The service is not per code.| 210*
1. INSTALL ADDRESS ON SERVICE.
2. PROVIDE FLASHING FOR MAST @ ROOF PENETRATION
3. TIGHTEN ALL RACEWAY FITTINGS.
4. BOND GAS PIPING FOR UNIT (NOT GAS MAIN)
5. BOND UNIT'S WATER PIPE
6. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE OR BURY MINIMUM 12"
7. NEED MINIMUM 3 0 COPPER FOR SERVICE CONDUCTORS (HOT'S)
8. IDENTIFY ALL NEUTRALS AT TERMINATIONS AND CLOSE TO WEATHERHEAD.
9. IDENTIFY SERVICE DISCONNECT.
10. WALL AT SUB-PANEL COVERED WITHOUT INSPECTION.
11. TIGHTEN ALL BUSHINGS AND SET SCREWS.