Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM04085
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/31/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/03/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER AFTER CORRECTIONS. 1. BOXES FOR FIRE ALARM CKTS TO BE IDENTIFIED RED 2. WIRING FOR FIRE ALARM CKTS TO BE RAN IN A NEAT AND WORKMAN LIKE MANNER FOLLOWING BUILDING SURFACE. 3. IDENTIFY WHITE USED AS HOT IN SWITCH LEGS 4. SEAL UNUSED OPENING IN BOX, NOTCH AND PROVIDE NAIL PLATES. |
|
12/05/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CEILING COVER-BOND SPRINKLER PIPE |
|
12/01/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SECURE FIXTURES TO GRID 2. DRYWALL/SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING CONNECTION AND TIGHTEN ALL GROUND SCREWS. 3. INSTALL BOX EXTENSION ON OVERFILLED BOXES. 4. MC TO BE SECURED WITHIN 12" OF TERMINATIONS. ALARM WIRING NOT IN |
|
11/29/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 4:15 DOOR LOCKED |
|
10/18/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WEST WALL COVER NOTE: J-NAILS NOT ALLOWED FOR MC - USE MC STRAPS NEC 110.3 |