Permit: T06CM04085

Parcel: 10612199B


Addresses:

1541 W PRINCE RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM04085

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/31/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/03/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER AFTER CORRECTIONS.
1. BOXES FOR FIRE ALARM CKTS TO BE IDENTIFIED RED
2. WIRING FOR FIRE ALARM CKTS TO BE RAN IN A NEAT AND WORKMAN LIKE MANNER FOLLOWING BUILDING SURFACE.
3. IDENTIFY WHITE USED AS HOT IN SWITCH LEGS
4. SEAL UNUSED OPENING IN BOX, NOTCH AND PROVIDE NAIL PLATES.
12/05/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CEILING COVER-BOND SPRINKLER PIPE
12/01/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SECURE FIXTURES TO GRID
2. DRYWALL/SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING CONNECTION AND TIGHTEN ALL GROUND SCREWS.
3. INSTALL BOX EXTENSION ON OVERFILLED BOXES.
4. MC TO BE SECURED WITHIN 12" OF TERMINATIONS.

ALARM WIRING NOT IN
11/29/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
4:15 DOOR LOCKED
10/18/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WEST WALL COVER
NOTE: J-NAILS NOT ALLOWED FOR MC - USE MC STRAPS
NEC 110.3