Permit: T06CM04082

Parcel: 107092230


Addresses:

455 W KELSO ST #236


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04082

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2007 ELECTRIC - FINAL Approved
08/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- REMOVE ALL COVERS IN QUESTION
- ELEC. CONTR. NOT ON SITE
07/30/2007 ELECTRIC - FINAL Cancelled IVRS - RI canceled
06/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRICAL CONTRACTOR TO BE ON SITE FOR INSPECTION
04/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MISSING NEUTRAL AT RECEPTACLE IN LIVING ROOM
2. NO POWER TO RECEPTACLE IN DINING AREA
3. CANNOT REMOVE PANEL COVER PAINTED & CAULKED TO WALL
4. ALL KITCHEN COUNTER TOP RECEPTACLES TO BE GFI PROTECTED PER NEC 210.8
5. INSTALL BOX EXTENSION ON RECEPTACLE UNDER SINK PER NEC 314.20
6. LENGTH OF CORD TO CONNECT DISHWASHER TO
BE 3FT TO 4FT PER NEC 422.16
7. GROUND ALL SWITCHES PER NEC 404.9
8. LABEL CIRCUITS AT PANEL PER NEC 408.4