Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04082
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2007 | ELECTRIC - FINAL | Approved | ||
08/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - REMOVE ALL COVERS IN QUESTION - ELEC. CONTR. NOT ON SITE |
|
07/30/2007 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
06/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRICAL CONTRACTOR TO BE ON SITE FOR INSPECTION |
|
04/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MISSING NEUTRAL AT RECEPTACLE IN LIVING ROOM 2. NO POWER TO RECEPTACLE IN DINING AREA 3. CANNOT REMOVE PANEL COVER PAINTED & CAULKED TO WALL 4. ALL KITCHEN COUNTER TOP RECEPTACLES TO BE GFI PROTECTED PER NEC 210.8 5. INSTALL BOX EXTENSION ON RECEPTACLE UNDER SINK PER NEC 314.20 6. LENGTH OF CORD TO CONNECT DISHWASHER TO BE 3FT TO 4FT PER NEC 422.16 7. GROUND ALL SWITCHES PER NEC 404.9 8. LABEL CIRCUITS AT PANEL PER NEC 408.4 |