Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2007 | ELECTRIC - FINAL | Approved | ||
| 08/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - REMOVE ALL COVERS IN QUESTION - ELEC. CONTR. NOT ON SITE |
|
| 04/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RECEPTACLES IN LIVING ROOM MISSING GROUND CONNECTION. 2. AFCI BREAKER ON CIRCUIT #4 DOES NOT TRIP WHEN TESTED. 3. INSTALL WALL PLATES ON DEVICES 4. CANNOT REMOVE PANEL COVER PAINTED & CAULKED TO WALL 5. ALL KITCHEN COUNTERTOP RECEPTACLES TO BE GFI PROTECTED PER NEC 210.8 6. INSTALL BOX EXTENSION ON RECEPTACLE UNDER SINK PER NEC 314.20 7. LENGTH OF CORD TO CONNECT DISHWASHER TO BE 3FT TO 4FT PER NEC 422.16 8. LABEL CIRCUITS AT PANEL PER NEC 408.4 9. GROUND ALL SWITCHES PER NEC 404.9 |