Inspection History Details
Inspection Status: Partial Approval
Inspection History: FIRE SPKLR - FINAL
Permit Number - T06CM04079
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2016 | FIRE SPKLR - FINAL | Partial Approval | In room under new facade with 25 foot roof, head blocked by I beam. Need to place another head on side of I beam to have enough coverage. All other heads in concealed spaces within facade have been visualized and approved. | |
06/06/2016 | FIRE SPKLR - FINAL | Partial Approval | Emergency lights and exit signs are operational / may stock and train only. | |
06/03/2016 | FIRE SPKLR - FINAL | Partial Approval | two more heads to be dropped in extension of hallway drop ceiling. submit as builds. Pending emergency lights / exit lighting passing on Monday 6/6/16, May stock and train only. No sales to take place until the fire alarm system is fully operative. |
|
11/13/2015 | FIRE SPKLR - FINAL | Partial Approval | 1. Sprinkler system is not properly monitored ( informed by contractor that the flow and tamper was monitored as burgler alarm) - must be monitored by a UL listed company and water flow should trigger a fire alarm response. Need panel indicating alarm, trouble or supervisory and must have a smoke and pull above the panel. 2. may not place merchandise in phase 1 area until all ceiling tiles have been put in place ( unless 24 hour fire watch is provided until all ceiling tiles have been placed). NS - 11/13/15 |