Permit: T06CM04050

Parcel: 141330300


Addresses:

10670 E GREEK DR


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM04050

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
02/01/2007 FRAMING Approved IVRS - Inspection :*
1) DRAWINGS ARE FOR WRONG SUB DIVISION, CAN YOU PLEASE CORRECT THIS BY NEXT INSPECTION
01/31/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
01/25/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LATH NOT COMPLETE AT REAR GABLE
2) ANCHOR BOLTS ON GARAGE SHEARWALL 3 HOLDOWN H REQUIRES 2" WASHERS
3) ANCHOR BOLT REQUIRED WITHIN 12" OF PLATE END GARAGE MAN DOOR
4) PLAN CALLS FOR KITCHEN SINK TO VENT TO ROOF
5) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF PLATE/STUD SURFACE
6) MASTER BATH REQUIRES CLEANOUT
7) HALL TOILET REQUIRES CLEANOUT AND VENT TO ROOF
8) BEDROOM 4 SHEAR WALL REQUIRES 2 HOLDOWNS AND 4 ANCHOR BOLTS