Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM04044
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 10/25/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PAPERWORK FOR TRUSS 7/DT2 2) SHEAR PANEL BLOCKING NAIL TO FLOOR 3) EXHAUST FAN DUCTS NOT SECURED AT T/TOPS 4) OK TO INSULATE |
|
| 10/23/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MORE NAILS IN PORCH TRUSS & TRUSS HANGERS 2) LOOSE NUTS AT H.D.'S 3) LOOSE LIGHT ROMEX IN ? PANTRY 4) SHEAR TRANSFER FOR INTERIOR SHEARWALLS 7/DT2. NEED BLK AT TOP OF PANEL NAILED TO FLOOR 5) ? STRAP AT DRYER DUCT 6) BATH CLOSE ROMEX OUT OF WALL 7) NEED FLOOR TRUSS FIX LIVING 8) NAIL ALL SHEARWALL PLATES 9) NEED DWV AND POTABLE H20 TESTS 10) EXHAUST FAN DUCT 2ND FLOOR BATH NOT SECURED TO ROOF JACK 11) BEND OVER THA HANGERS AT GIRDER TRUSS |