Permit: T06CM04043

Parcel: 122030300


Addresses:

4556 E SENECA ST

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
03/28/2007 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
03/27/2007 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PER DETAIL A/2 EXISTING DEN EPOXY INTO EXISTING FOOTER
2) NO HOLDOWNS (HPAHD-22)
02/01/2007 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/30/2007 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TOO WET TO INSPECT
01/19/2007 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
EXPOSE BEARING FOOTERS AND PLUMBERS
ROUGH DEN
ALL WORK COVERED WITHOUT INSPECTION
MUST BE EXPOSED
PROVIDE 10' HEAD TEST EXISTING PLUMBING
AT NEW ADDITION
NO HOLDDOWNS AT THIS TIME
01/17/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) EXPOSE FTG AT DEN AND PLUMBING FOR INSPECTION
2) BEARING FTG SHALL BE 12" X 12" MINIMUM-12" BELOW GRADE