Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EQUIPMENT GROUND TO J-BOX TO HOUSE PANEL IS UNDERSIZED - NEC 250.122 B 2. GROUND TO J-BOX UNDERSIZED - NEC 250.122B 3. PLANS SHOW #8's TO CONTINUE TO CONTROL ENCLOSURE 4. PLANS DO NOT SHOW CKT FOR BUBBLER 5. UNDERGROUND TO TANK COVERED WITHOUT INSPECTION 6. TANK IN USE BEFORE APPROVAL, CAN'T INSPECT J-BOX OR PUMPS 7. SEAL OFF'S TO BE WITHIN 18" OF ENCLOSURE AND USED AS LISTED, DO NOT LAY HORIZONTALLY 8. WIRING METHOD TANK TO PANEL TO MEET THE REQUIREMENTS OF NEC ARTICLE SOL CLASS 1 DIVISION 1 PARTIAL INSPECTION |
|
| 03/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ALL UNITS INTERIOR 1. SEWAGE EJECTION SYSTEM TO BE PART OF APPROVED PLAN WILL INSPECT WHEN IT IS. |
|
| 03/13/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/29/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK UNIT #102 FINAL OK LOCK OUT |
|
| 01/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR #102 ONLY 1. DIRECTORY NOT IDENTIFIED 2. NEED LOCKOUT LISTED FOR PANEL 3. CHECK SAME CORRECTIONS OTHER UNITS |
|
| 01/09/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FINAL UNITS #106 & #124 |
|
| 01/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION UNIT #106 & #107 1. EMERGENCY LIGHT TO BE FED BY CKT FOR AREA - NEC 700.12 2. COOLER WIRING NOT COMPLETE 3. PROVIDE DISCONNECT OR INSTA HOT - NEC 422 |
|
| 01/04/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |