Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 11/16/2007 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* | |
| 11/14/2007 | ELECTRIC - CABLE DROP | Denied | INSPECTION FOR SERVICE, FEEDERS AND SUB-PANELS ONLY 1. INSTALL PANIC HARDWARE FOR EXIT DOOR - NEC 110.26 C2 2. SPRINKLER PIPING NOT ALLOWED IN DEDICATED SPACE ABOVE SERVICE - NEC 110.26F1 3. SERVICE CONDUCTORS UNDERSIZED - PLAN CALLS FOR #600 CU/NOT #500 4. EQUIPMENT GROUNDS #6 & SMALLER TO BE GREEN ENTIRE LENGTH - NEC 250.119 5. POST BOND FOR TEMP. POWER FOR UNITS PARTIAL INSPECTION |