Permit: T06CM04038

Parcel: 108252430

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM04038

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
04/19/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
4" CO IN GARAGE OK TO COVER
04/17/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER WALLS EXCEPT AT 4" CO AT GARAGE
RETEST 4" CO TO 2ND LEVEL
STILL NEED PLAN REV. FOR AAV
STILL NEED SHWR PAN INSP.
04/13/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. A VENT SHALL RISE VERTICALLY TO A POINT NOT LESS THAN 6" ABOVE THE OVERFLOW OF THE FIXTURE BEING SERVED BEFORE OFFSETTING HORIZONTALLY.
2. WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN, IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE DOWN STREAM OF THE TRAP BEING SERVED.
04/10/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/06/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PLUMBERS STILL WORKING
2) AAV REQUIRES PLAN REVISION
3) THIS BLDG HAS 4 WC AND REQUIRES 12-56" OF VENTING THROUGH OUT SYSTEM
4) 3/4" WATER SUPPLY PER PLAN AT W.B.
04/05/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
WATER LEAK AT 4" CLEANOUT, MAY BE BELOW SLAB
WET AT FLOOR BOTH DAYS
3" IN GARAGE W/TEMP CAP
1ST FLOOR VENTS NOT UNDER TEST
UNVENTED P-TRAPS
1/4 BENDS ON HORIZONTAL
USE PROPER ALIGNMENT
12.47 SQ" OF VENTING REQUIRED THROUGHOUT SYSTEM CLEANOUTS

CUT PIPING SQUARE AND REMOVE BURRS
04/04/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PROVIDE TEST ON WATER & WASTE
DRAINAGE FITTINGS REQUIRED ON VENTS BELOW FLOOD LEVEL.
T&P
NOT A COMPLETE LIST