Permit: T06CM04029

Parcel: 108252350

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM04029

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/21/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
SUPPORT OF CONDENSATE PIPING NOT TO EXCEED 4'
OK FOR FINAL
09/20/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DISCHARGE SIDE OF P-TRAP NEEDS TO BE LOWER THAN INLET PER MANUFACTURER INSTRUCTIONS
2) AC-1 DOES NOT HAVE PROPER SLOPE, SUPPORT COND. PIPING EVERY 4'
09/14/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*