Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04028
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SMOKE DETECTORS NOT INTER-CONNECTED 2. SMOKE DETECTOR TO BE MIN. 36" FROM HVAC VENT IN HALL |
|
08/22/2007 | ELECTRIC - FINAL | Partial Approval | ALL ELECTRICAL OK REPAIR AC & INSTALL STAT CALL BACK FOR COMPLETE OCCUPANCY STATUS |
|
08/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - REPAIR AIR HANDLER HANGING BY FLEX CONDUIT - REMOVE SWITCH COVER PLATES, ALSO, PER NOTES #5 & #6 - ELEC. CONTR. NOT ON SITE |
|
06/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRICAL CONTRACTOR TO BE ON SITE FOR INSPECTION |
|
04/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL ALL SWITCHES 2. INSTALL WALL PLATES AT DEVICES 3. GROUND ALL SWITCHES PER NEC 404.9 4. ALL KITCHEN COUNTERTOP RECEPTACLES TO BE GFI PROTECTED PER NEC 210.8 5. INSTALL BOX EXTENSION ON RECEPTACLE UNDER SINK PER NEC 314.20 6. LENGTH OF CORD TO CONNECT DISHWASHER TO BE 3 FT TO 4FT PER NEC 422.16 7. INSTALL PANEL COVER |