Permit: T06CM04028

Parcel: 107092230


Addresses:

455 W KELSO ST #234


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04028

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SMOKE DETECTORS NOT INTER-CONNECTED
2. SMOKE DETECTOR TO BE MIN. 36" FROM HVAC VENT IN HALL
08/22/2007 ELECTRIC - FINAL Partial Approval ALL ELECTRICAL OK
REPAIR AC & INSTALL STAT
CALL BACK FOR COMPLETE OCCUPANCY STATUS
08/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- REPAIR AIR HANDLER HANGING BY FLEX CONDUIT
- REMOVE SWITCH COVER PLATES, ALSO, PER NOTES #5 & #6
- ELEC. CONTR. NOT ON SITE
06/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRICAL CONTRACTOR TO BE ON SITE FOR INSPECTION
04/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL ALL SWITCHES
2. INSTALL WALL PLATES AT DEVICES
3. GROUND ALL SWITCHES PER NEC 404.9
4. ALL KITCHEN COUNTERTOP RECEPTACLES TO BE GFI PROTECTED PER NEC 210.8
5. INSTALL BOX EXTENSION ON RECEPTACLE UNDER SINK PER NEC 314.20
6. LENGTH OF CORD TO CONNECT DISHWASHER TO BE 3 FT TO 4FT PER NEC 422.16
7. INSTALL PANEL COVER